HydroFixx up to 10.8 m³/h / 47.5 gpm
250 kW / 853 MBH at ΔT 20 K
The manifold with integrated hydronic junction
Chamber size: | 160/160 |
Heating water flow rate: | 10.8 m³/h / 47.5 gpm |
Output at ∆T 20 K: | 250 kW / 853 MBH |
Largest connetion: | DN 65 / 2 1/2" |
Boiler connection: | up to DN 80 / 3" |
Pipe distance (OC) | 250 mm, 300mm, variable / 9.8", 11.8", variable |
Product description
Combined flow and return manifold with chambers arranged adjacent to each other, separated by sinusoidal partition wall, with horizontally welded-on hydraulic separator located directly below.
Consisting of square profiles S235, wall thickness 4 mm. The HydroFixx is pressure-tested and primed at the factory. Operating pressure max. 6 bar, operating temperature max. 110°C.
- The supply from/to the heating boiler is possible both from the top onto the compact manifold and from the bottom to the hydraulic separator.
- Heating circuit connections as threaded and / or flanged connectors PN 6 / PN 16 and aligned to the height of the shut-off valves.
- With downward-running sludge trap with 1" desludging sleeve.
Accessories
Stand bracket

For chamber size
| Bottom plate | Head plate | Adjustable in height |
---|---|---|---|
[mm] | [mm] | [mm] | [mm] |
120/120 to 200/200 |
150 x 150 | 120 x 120 | from 270 to 340 |
280/320 to 500/550 | 200 x 200 |
150 x 180 |
from 270 to 340 |
Soundproof and zinc-plated, consisting of bottom plate with stand pipe and head plate
with guide pipe incl. connecting screws, adjustable in height.
Wall bracket

For chamber size
| Head plate |
Outreach |
---|---|---|
[mm] | [mm] | [mm] |
120/120 to 200/200 |
120 x 120 | 300 |
280/320 to 500/550 | 150 x 180 |
500 |
Soundproof and zinc-plated, consisting of wall panel for screw fastening,
bracket and head plate.
Thermal insulation

For chamber size
| PUR foam in coarse grain aluminium casing | PUR foam in galvanized sheet steel casing | Mineral wool in galvanized sheet steel casing |
---|---|---|---|
[mm] | [Insulation thickness in mm] | [Insulation thickness in mm] | [Insulation thickness in mm] |
120/120 to 200/200 |
60 | - | 100 |
280/320 to 500/550 | - | 60 | 100 |
In compliance with EnEV 2014 consisting of half shells with end pieces and cutouts for all nozzles
Magnetite separation module - Flange

Attention: All magnetite separation modules in flange-type design are not suitable for retrofitting.
For separation of ferromagnetic substances.
Consisting of an additional flanged connector DN 125 PN 6, equipped with sealing, screws, nuts, and blind flange fitted with magnetite filter bars, depending on the size of the selected HydroFixx.
Draining gutter

Made of galvanized sheet steel, size: 100/125/100 mm with 2" drain sieve.
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized
(max. outreach 200 mm)
Identification plate

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line
Technical data
Heating water throughput rate
|
Output at
ΔT 20 K |
Manifold chamber
| Water quantity Manifold | Water quantity Low loss header |
Heat transfer at 70°/50°C |
Return flow boost |
Wall thickness | |
---|---|---|---|---|---|---|---|---|
[m³/h] | [kW] | [Width / Height] | [l/rm] | [l/rm] | [kW] | [%] | [K] | [mm] |
10.8 | 250 | 160/160 | 10.9 | 11.5 | 3.7 | 1.5 | 0.3 | 4 |