Compact manifolds up to 25.8 m³/h / 113.6 gpm
600 kW / 2,047.3 MBH at ΔT 20 K
Chamber size: | 200/120 |
Heating water flow rate: | 25.8 m³/h / 113.6 gpm |
Output at ∆T 20 K: | 600 kW / 2,047.3 MBH |
Largest connection: | DN 100 / 4" |
Boiler connection: | up to DN 125 / 5" |
Pipe distance (OC): |
250 mm, 300 mm or 350 mm / |
Operating pressure: | max. 6 bar / max. 87 psi |
Operating temperature: | max. 110°C / max. 230°F |
Product description
Combined flow and return manifold, consisting of rectangular tube 200 x 120 mm, with chambers arranged adjacent to each other, separated by sinusoidal partition wall and made of black sheet steel S235. The compact manifold is pressure-tested and primed at the factory.
- Connections as threaded and/or flanged connections ANSI 150lbs.
- All connections are aligned to the height of the shut-off valves and optionally available from the top, the side or the bottom.
- Drain connection couplings 1/2" for flow and return line chamber are a standard feature.
Accessories
Stand bracket
For chamber size
| Bottom plate | Head plate | Adjustable in height |
---|---|---|---|
[mm] | [mm] | [mm] | [mm] |
120/80 to 160/80 |
150 x 150 | 120 x 120 | from 405 to 600 |
180/110 to 200/120 | 150 x 150 | 120 x 120 | from 270 to 340 |
280/180 to 700/500 | 200 x 200 | 150 x 180 | from 270 to 340 |
Soundproof and zinc-plated, consisting of bottom plate with stand pipe and head plate with guide pipe incl. connecting screws, adjustable in height.
Wall bracket
For chamber size
| Head plate |
Outreach up to manifold centre |
---|---|---|
[mm] | [mm] | [mm] |
120/80 to 160/80 |
120 x 120 | 220 |
180/110 to 200/120 | 120 x 120 |
300 |
280/180 to 700/500 | 150 x 180 |
500 |
Soundproof and zinc-plated, consisting of wall panel for screw fastening, bracket and head plate.
Thermal insulation
For chamber size
| PUR foam in coarse grain aluminium casing | PUR foam in galvanized sheet steel casing | Mineral wool in galvanized sheet steel casing |
---|---|---|---|
[mm] | [Insulation thickness in mm] | [Insulation thickness in mm] | [Insulation thickness in mm] |
120/80 to 200/120 |
45 | 45 | 100 |
280/180 to 300/200 | 50 | 50 | 100 |
400/200 to 700/500 | - | 60 | 100 |
In compliance with EnEV 2014 consisting of half shells with end pieces and cutouts for all nozzles.
Draining gutter
Made of galvanized sheet steel, size: 100/125/100 mm with 2" drain sieve
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized (max. outreach 200 mm)
Identification plate
Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line
Technical data
Heating water flow rate
|
Output at
ΔT 20 K |
Manifold chamber
| Water quantity |
Heat transfer at 70°/50°C |
Return flow boost |
Wall thickness |
Weight | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
[m³/h] | [gpm] | [kW] | [MBH] | [Width / Height] | [l] | [gal/ |
[kW] | [Btu] | [%] | [K] | [mm] | [in inch] | [kg/rm) | [lbs/rm] |
25.8 | 113.6 | 600 | 2,047.3 | 200/120 | 21.5 | 5.7 | 4.3 | 14.7 | 1.0 | 0.2 | 4 | 0.2 | 22.6 | 49.8 |