Small manifold up to 70 kW / 238.9 Btu

incl. EPP insulation and wall bracket


Chamber size: 80/60
Connection: union nut
Heating water throughput rate: 3.0 m³/h / 10.7 gpm
Output at ∆t 20K: 70 kW / 238.9 Btu
Pipe distance (OC): 125 mm / 4 11/16"
Operating pressure: max. 4 bar / max. 58 psi
Operating temperature: max. 110°C / max. 230°F
Product description

Combined flow and return manifold consisting of rectangular tubing with chambers made of black sheet steel S235
arranged adjacent to one another and separated by sinusoidal parting wall. The compact manifold is factory pressure
tested and primed.

  • Connection, heating circuits: Flare 1 1/2“ union nut
  • Connection, boiler circuits: 1 1/2" NPT
Accessories

Thermal insulation, included in the set

Wärmedämmung
For chamber sizeEPP foam (black)
[mm] [Insulation thickness in mm]
60/60
32
80/60 36
120/80 52

In compliance with EnEV 2014 consisting of half shells with end pieces and cutouts for all nozzles.

 

Wall bracket, included in the set

Bezeichnungsschild

Soundproof and zinc-plated, consisting of wall panel for screw fastening and bracket, outreach up to manifold centre: 160 mm

(2 wall brackets are included in each set)

 

Maintenance box - Magnetite separation module

Anschluss am Kesselrücklauf unter dem Verteiler

Enables desludging with pressurized system. Consisting of section tube 80x60, material S235, connection: 2x G 1 ½“. Equipped with desludging nozzle and ball valve ½“, and magnetic rod screwed into the thermwell. For attachment to the boiler return line beneath the manifold.

Set components: EPP insulation in compliance with EnEV, ball valve, magnetite filter cartridge

Identification plate

Bezeichnungsschild

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line

Technical data
Output at
ΔT 20 K
 
Number of heating circuitsHeating water throughput rateLengthWater quantity

Heat transfer at 70°/50°C

Return flow boost

Wall thickness

 

[kW] [Btu] [HK] [m³/h] [gpm] [mm] [in inch] [l] [gal] [kW] [Btu] [%] [K] [mm] [in inch]
70 238.9 2 3.0 10.7 475 18.7 1.9 0.50 1.0 3.41 1.5 0.3 2.5 1/10"
70 238.9 3 3.0 10.7 725 28.5 3.0 0.79 1.5 5.12 2.1 0.4 2.5 1/10"
70 238.9 4 3.0 10.7 975 38.4 4.0 1.06 1.9 6.48 2.8 0.6 2.5 1/10"
70 238.9 5 3.0 10.7 1,225 48.2 5.0 1.32 2.4 8.19 3.5 0.7 2.5 1/10"
70 238.9 6 3.0 10.7 1,475 58.1 6.0 1.59 2.9 9.90 4.2 0.8 2.5 1/10"
Downloads

Technical information

Your direct line

Any questions or comments?

We will be pleased to offer advice and answer any questions concerning our product range.

Just write us a message or contact us by phone:
519-748-6788.